Useful Resources

No. of PhasesMain Breaker sizeMax. ExportMax. Inverter sizeMax. Battery charge
140A2.3kW9.2kW10A
160A3.45kW13.8kW15A
180A4.6kW18.4kW20A
340A6.9kW (3P inv.)27.7kW (9.2kW/phase)10A
350A8.6kW (3P inv.)35kW (11.5kW/phase)12.5A
360A10.4kW (3P inv.)41.6kW (13.8kW/phase)15A
380A13.9kW (3P inv.)55.4kW (18.4kW/phase)20A
3100A17.3kW (3P inv.)69.3kW (23kW/phase)25A
Maximum individual installation limits in a shared LV (400V/230V) feeder as derived from NRS 097-2-3

Going Solar with the City of Cape Town

GuidelineĀ for Electrical Contractors

List of Approved PV Inverters

Electricity supply by-law

Technical Standard for the Interconnection of Embedded Generation